Up Burn Type Hot Water Boiler

Name
Up Burn Type Hot Water Boiler
Model
KW-400S
Category
Hot Water Boiler / Up Burn Type Hot Water Boiler

Share
Share to Facebook Share to Google Share to Twitter Share to Linkedin

Product Specification
TypeKW- 400S
Heat outputkcaℓ/h
400000
Water flow rate (50℃ vertical lift)l/h
8000
Boiler efficiency%
90
Boiler bodyType/
Water Tube Type
Water contentL
275
Heat surface aream2
8.9
Max. working pressurekgf/cm2
10
Boiler model 
Small type boiler
BurnerCombustion method/
ON-OFF
Type/
Separate type (Force draft fan)
Fuel consumptionDieselℓ/h
52.9
Ignite type/
High electric spark
Power of equipmentKW
2.3
ControlCombustion control/
Full automatic ignition, combustion (Misfiring will automatic running stop)
Temperature control/
Electronic digital display temperature controller (upper limit / lower limit selectable)
Safety devices/
Misfiring, excess fuel temperature, pressure switch and safety combustion protection, pump is abnormal.
ConnectionFeed water pipemm
65
Feedback water pipe
65
Blowdown pipe
25
Chimney diameterø mm
290
Fuel inletDieselmm
15
SizeBoiler dimensions(L)mm
1640
(W)
1122
(H)
2014
NOTES:
1. Standard power is 3Phase/220V/60HZ. Notice of change, if any, is required.
2. Fuel type:KW-Diesel.
3. Fuel consumption is calculated at low heat value : Diesel=8400 kcal/l.
4. Products partial modification for improvement is allowed without notice.
5. Boiler efficiency tolerance value±1%. Boiler dimension tolerance value±1%.