KG-1500

Name
Dual Fuel Steam Boiler
Model
KG-1500
Category
Steam Boiler / Dual Fuel Steam Boiler

Share
Share to Facebook Share to Google Share to Twitter Share to Linkedin

Product Specification
MODEL
KG-1500
PERFORMANCEEQUIVALENT OUTPUTkg/h 1500
HEAT OUTPUTkcal/h 808000
HEATING SURFACE AREAm2 9.9
MAX.PRESSUREkgf/cm2 10
WATER CONTENTL 176
BOILER EFFICIENCY% 92
WATER PREHEATER INCLUDE
COMBUSTION TYPE  TWO-STAGE
FUEL CONSUMPTION 13ANm3/h 88.7
LPG Propanekg/h 76.6
LPG Butane 80.6
DIESELl/h 104.6
POWER OF EQUIPMENTkw 8.5
POWER OF AUXILIARY EQUIPMENTSWATER PUMP MOTORkw 2.2
EXHAUSTING FAN MOTOR 5.5
INJECTION PUMP MOTOR 0.4
CONTROL PANEL 0.4
PRODUCT WEIGHTkg 1800
PIPE DIAMETERSFUEL INLET DIAMETER 13Amm 50
LPG 40
DIESEL 25
FEED WATER INLET DIAMETER 25
STEAM OUTLET DIAMETER 50
BOILER-WATER DRAIN DIAMETER 25
SAFETY VALVE OUTLET DIAMETER  25&25
AUTO BLOWDOWN DIAMETER 10
CHIMNEY DIAMETERψmm 360
POWER WIRE INLET DIAMETERmm2 8
SIZEBOILER
DIMENSIONS
LENGTHmm 1970
WIDTH 1915
HEIGHT 2210

 

NOTES:
1. KG- x x x indicates diesel and gas double fuel steam boiler.
2. Standard power is 3Phase/220V/60HZ. Notice of change is required.
3.

Fuel consumption is calculated at low heat value:

13A:9900 kcal/Nm3 , LPG Propane:11460 kcal/kg ,LPG Butane:10900 kcal/kg ,DIESEL 8400kcal / l.

4.

(1000kg/h~2000kg/h model) supply pressure 0.8~3.5kgf/cm2. Installation of pressure reducing device, gas entrance to the boiler to reduce 400~1000mmAq.

Low pressure supply should be stable, pressure dropping can't be too much, and the gas flow should be enough.

5. Partial product improvement may be made without notice.
6. The error allow value of boiler efficiency is ±1%.

 

Related Products