Dual Fuel Steam Boiler

Name
Dual Fuel Steam Boiler
Model
KG-2500
Category
Steam Boiler / Dual Fuel Steam Boiler

Share
Share to Facebook Share to Google Share to Twitter Share to Linkedin

Product Specification
MODEL
KG-2500
PERFORMANCEEQUIVALENT OUTPUTkg/h 2500
HEAT OUTPUTkcal/h 1347000
HEATING SURFACE AREAm2 15.4
MAX.PRESSUREkgf/cm2 10
WATER CONTENTL 206
BOILER EFFICIENCY% 92
WATER PREHEATER INCLUDE
COMBUSTION TYPE  TWO-STAGE
FUEL CONSUMPTION 13ANm3/h 147.9
LPG Propanekg/h 127.8
LPG Butane 134.3
DIESELl/h 174.3
POWER OF EQUIPMENTkw 15.7
POWER OF AUXILIARY EQUIPMENTSWATER PUMP MOTORkw 3.7
EXHAUSTING FAN MOTOR 11
INJECTION PUMP MOTOR 0.4
CONTROL PANEL 0.6
PRODUCT WEIGHTkg 2560
PIPE DIAMETERSFUEL INLET DIAMETER 13Amm 50
LPG 50
DIESEL 25
FEED WATER INLET DIAMETER 40
STEAM OUTLET DIAMETER 65
BOILER-WATER DRAIN DIAMETER 25
SAFETY VALVE OUTLET DIAMETER  32&32
AUTO BLOWDOWN DIAMETER 10
CHIMNEY DIAMETERψmm 400
POWER WIRE INLET DIAMETERmm2 14
SIZEBOILER
DIMENSIONS
LENGTHmm 2070
WIDTH 1940
HEIGHT 2430

 

NOTES:
1. KG- x x x indicates diesel and gas double fuel steam boiler.
2. Standard power is 3Phase/220V/60HZ. Notice of change is required.
3.

Fuel consumption is calculated at low heat value: 

13A:9900 kcal/Nm3 , LPG Propane:11460 kcal/kg ,LPG Butane:10900 kcal/kg ,DIESEL: 8400kcal / l.

4.

(2500kg/h~3000kg/h) model supply pressure 0.8~3.5 kgf/cm2, gas entrance to the boiler to reduce 900~1400mmAq.

Low pressure supply should be stable, pressure dropping can't be too much, and the gas flow should be enough.

5. Partial product improvement may be made without notice.
6. The error allow value of boiler efficiency is ±1%.

 

Related Products